广州菱控|三菱
当前位置:首页 >> 技术支持 >> QJ71C24 R2与E540变频器通信问题
QJ71C24 R2与E540变频器通信问题  时间:2014/3/8 16:41:00
QJ71C24 R2与E540变频器进行232通信,QJ发送后变频器无反应,在电脑上用串口调试工具发送同样的数据,变频器动作正常。将QJ的端口连接至电脑端口后用串口调试工具对其发送内容进行检测后发现并无错误,只是获得的数据并不是一起接收到得。先将串口调试工具获得的内容粘贴如下:
# Time Function Data ( Hex )
16 [00010541] IRP_MJ_READ Length: 0001, Data: 05
17 [00010541] IRP_MJ_READ Length: 0001, Data: 30
18 [00010541] IRP_MJ_READ Length: 0001, Data: 30
19 [00010541] IRP_MJ_READ Length: 0001, Data: 46
20 [00010541] IRP_MJ_READ Length: 0001, Data: 41
21 [00010541] IRP_MJ_READ Length: 0001, Data: 31
22 [00010541] IRP_MJ_READ Length: 0001, Data: 30
23 [00010541] IRP_MJ_READ Length: 0001, Data: 30
24 [00010541] IRP_MJ_READ Length: 0001, Data: 37
25 [00010541] IRP_MJ_READ Length: 0001, Data: 38
26 [00010542] IRP_MJ_READ Length: 0001, Data: 0D
27 [00010543] IRP_MJ_READ Length: 0001, Data: 0A
注:以上是串口调试工具获得QJ发送的数据记录,这个是变频停止指令(用串口调试工具让变频器先运转起来后再用此指令),即使是变频器运行指令,变频器也无反应。为什么接收来的数据时这个样子呢??而不是一个长度为12的数据呢??
138 [00003133] IRP_MJ_WRITE Length: 0012, Data: 05 30 30 46 41 31 30 32 37 41 0D 0A
139 [00003136] IRP_MJ_READ Length: 0003, Data: 06 30 30
140 [00004015] IRP_MJ_WRITE Length: 0012, Data: 05 30 30 46 41 31 30 30 37 38 0D 0A
141 [00004018] IRP_MJ_READ Length: 0003, Data: 06 30 30
142 [00007181] IRP_MJ_WRITE Length: 0012, Data: 05 30 30 46 41 31 30 32 37 41 0D 0A
143 [00007184] IRP_MJ_READ Length: 0003, Data: 06 30 30
注:以上是有串口调试工具向E540发送同样的数据 E540动作正常
通信设置 9600、8、 Even 、2。 QJ(SW3:05DE SW4:0006)、 E540(0号站 9600、8、even、2、CRLF结束符、通信次数为9999 )、串口调试工具均设置无误
Re:续:QJ71C24 R2与E540变频器通信问题  时间:2014/3/8 19:55:00
该问题由『变频调速器』版块回答,请到相应版块咨询,敬请谅解。