When connecting a two-wire type sensor or input equipment containing a
parallel resistor, select a sensor or equipment whose leakage current is 1.7mA
or less.
If the leakage current is more than 1.7mA, connect a bleeder resistor obtained
in the following calculation formula.
Circuit image
The power capacity W of the bleeder resistor R is as follows:
• Please set the response speed (DIP switch) according to the ON or OFF time
of the input signal.
When setting 1.5 ms:
Set both the ON and OFF time of the input signal to 1.5 ms or more.
When setting 0.5 ms:
Set both the ON and OFF time of the input signal to 0.5 ms or more.
5. Specifications
5.1 General specifications
Item Specification
Ambient
working
temperature
0 to 55°C (32 to 131°F)
Ambient storage
temperature
-25 to 75°C (-13 to 167°F)
Ambient
operating
humidity
5 to 95%RH: Dew condensation shall not be considered.
Ambient storage
humidity
5 to 95%RH: Dew condensation shall not be considered.
Vibration
resistance
When intermittent vibration is present
Number of times of
sweep
Frequency Acceleration Half amplitude
10 times in each of
X, Y and Z directions
(for 80 min)
10 to 57Hz − 0.075mm
57 to 150Hz 9.8m/s2 −
When continuous vibration is present
Frequency Acceleration Half amplitude
10 to 57Hz − 0.035mm
R
24V DC
Leakage
current
Input impedance
5.6 kΩ
1.7 mA or less
R: Bleeder resistor
Sensor Unit
Detection
circuit
1.7(mA)
Leakage current(mA) - 1.7(mA)
R(kΩ) < × 5.6(kΩ)
(Input voltage)
2
R
W =
for which electrical power is supplied from fixed facilities.
The surge voltage withstand level for up to the rated voltage of 300V is 2500V.
*4 This index indicates the degree of conductive generating substances in the
environment in which the module is used. The degree of contamination 2
indicates that contamination is caused by generation of only non-conductive
substances.
In this degree, however, temporary conduction may be caused by accidental
condensation.
5.2 Input specifications
5.3 Performance specifications
Item Specification
Input method DC input (External power supply of the input part)
Number of inputs 4 points
Isolation method Isolation with photocoupler
Rated input voltage 24V DC
Rated input current Approx. 4 mA
Operating voltage range
20.4 to 28.8V DC (24V DC -15% to +20%)
Ripple ratio: Within 5%
Max. simultaneous ON
input points
100% (at 24V DC)
ON voltage/ON current 19 V or more/3 mA or more
OFF voltage/OFF current 11 V or less/1.7 mA or less
Input resistance 5.6 kΩ
Response
time
OFF→ON 0.5ms/1.5 ms or less (at 24V DC)
Selected by DIP switch (default value = OFF/1.5ms).
ON→OFF
0.5ms/1.5 ms or less (at 24V DC)
Selected by DIP switch (default value = OFF/1.5ms).
Common wiring method
4 points/1 common (2 points)
(terminal block two-wire type)
Item Specification
Module
power
supply
Vol tage
20.4 to 28.8V DC (24V DC -15% to +20%)
Ripple ratio: Within 5%
Current
consumption
40mA (when all points are ON)
Initial current 70mA
Max. allowable
momentary power
failure period
PS1:1ms
Number of stations
occupied
4-, 8- or 16-point mode: 1 station
Noise durability
500Vp-p
Noise width: 1µs Cycle: 25 to 60 Hz
(by noise simulator)
Withstand voltage
500V AC for 1 min between primary area (external
DC terminal) and secondary area (internal circuit)
10 MΩ or more between primary area (external
60.