资料介绍:
c
withstand
voltage
500V AC for 1 min In conformance to JEM-1021
Between case and PLC grounding
terminal Isolation
resistance
5 MΩ or more by 500V
DC megger
Operating
ambience
Do not use in environment with corrosive gas, flammable gas
or conductive dusts.
Working altitude < 2000m*1
Grounding
Grounding resistance 100Ω or less (Common grounding with
strong electrical systems is not allowed.)
Item Specification Remarks
Communication
speed
2.5Mbps 625kbps 156kbps --
Distance between
stations
No restriction --
Maximum number of
modules connected
in 1 drop line
8 units --
Maximum trunk
length
35m
(114' 9")
100m
(328' 1")
500m
(1640' 5")
Cable length between
terminating resistors
T-branch interval No restriction --
Maximum drop
length
4m(13' 1")
16m
(52' 5")
60m
(196' 10")
Cable length per
branch
Cumulative drop line
length
15m
(49' 2")
50m
(164' 0")
200m
(656' 2")
Sum of all drop lines
Master station
Terminating
resistor
T branch
connection T-branch interval
Power
adapter
Remote
I/O station
Remote
I/O station
Drop length
(including branch)
Remote
I/O station
Remote
I/O station
Remote
I/O station
Remote
I/O station
Distance between
stations
Terminating
resistor
Trunk length (branch line length not included)
Trunk line
Drop line
5.3 Performance specifications
*1 When connected to the FX1N Series PLC, up to two FX2N-64CL-M units can be
connected to the main unit and another two on the extension unit.
*2 FX2N-64CL-M draws 190mA from the 5V DC source.
The total 5V consumption of all special function blocks connected to the main
unit or extension unit must not exceed the 5V source capacity of the system.
(Refer to the Hardware manual of the PLC)
*3 Up to 7 units can be connected to an FX3UC-32MT-LT PLC.
*4 For the VCTF cable specifications, refer to the FX2N-64CL-