) Tool
For tightening the terminal, use a
commercially available small
screwdriver having a straight form that is
not widened toward the end as shown
right.
Caution:
If the diameter of screwdriver grip is too
small, tightening torque will not be able
to be achieved. Use the following recommended screwdriver or an
appropriate replacement (grip diameter: approximately 25mm (0.98")).
2 Wiring of Analog Output
→ For the terminal configuration, refer to Subsection 1.2.1
1 Use 2-core shielded twisted pair cable for the analog output lines, and
separate the analog output lines from other power lines or inductive lines.
2 The grounding resistance should be 100Ω or less.
3 Grounding
Grounding should be performed as stated below.
• The grounding resistance should be 100Ω or less.
• Independent grounding should be performed for best results.
When independent grounding is not performed, perform "shared
grounding" of the following figure.
→ For details, refer to the FX3G Series User's
Manual - Hardware Edition.
• The grounding wire size should be AWG 22-20 (0.3-0.5 mm2).
• The grounding point should be close to the PLC, and all grounding wire
should be as short as possible.
Manufacturer Model
Phoenix Contact Co., Ltd. SZS 0.4×2.5
With
straight tip
2.5mm
(0.1")
0.4mm
(0.02")
Using voltage
output
1DA-BD
VI-
Terminal
block
V+
I+
Grounding
Using current
output
1DA-BD
VI-
Terminal
block
V+
I+
Grounding
PLC PLC PLC Other
equipment
Shared grounding
Good condition
Common grounding
Not allowed
Independent grounding
Best condition
Other
equipment
Other
equipment
4. Specifications
4.1 Applicable PLC
The version number can be checked by monitoring D8001 as the last three digits
indicate it.
• The number of connectable expansion boards varies depending on the main unit as
follows:
FX3G-14M…, 24M… Main units : 1 unit
FX3G-40M…, 60M… Main units : 2 units
Never stack up two or more expansion boards.
For details on the system configuration, refer to the following manual.
→ Refer to the FX3G/FX3U/FX3UC Series User's Manual - Analog Control Edition
4.2 General Specifications
The general specifications are equivalent to the PLC main unit.
For general specifications, refer to the following manuals.
→ Refer to the FX3G Series User's Manual - Hardware Edition
4.3 Performance Specifications
STARTUP AND
MAINTENANCE
PRECAUTIONS
• Do not disassemble or modify the PLC.
Doing so may cause fire, equipment failures, or malfunctions.
* For repair, contact your local Mitsubishi Electric distributor.
• Do not drop the product or exert strong impact to it.
Doing so may cause damage.
DISPOSAL
PRECAUTIONS
• Please contact a certified electronic waste disposal company for the
environmentally safe recycling and disposal of your device.
TRANSPORT AND
STORAGE PRECAUTIONS
• The product is a precision instrument. During transportation, avoid any impacts.
Failure to do so may cause failures in the product. After transportation, verify the
operations of the product.
Model name Applicability
FX3G Series PLC Ver. 1.10 or later
Item
Specifications
Voltage output Current output
Analog output
range
0 to 10V DC
(External load resistance:
2kΩ to 1MΩ)
4 to 20mA DC
(External load resistance:
500Ω or less)
Digital input 12 bits, binary 11 bits, binary
Resolution 2.5mV(10V/4000) 8μA(16mA/2000)
•±0.5%(±50mV) for full scale
of 10V(when ambient
temperature is 25°C±5°C)
•±1.0% (±100mV) for full
scale of 10V
(when ambient temperature
is 0°C to 55°C)
4.4 List of Special Devices
As for the details of the special devices, refer to the following man
→ Refer to the FX3G/FX3U/ FX3UC Series User's Manual - Ana
output
characteristics
0 to 4000 are adjusted to 0 to
10V when the external load
resistance is 2kΩ.
0 to 2000 ar
20mA when
resistance is
Insulation
method No insulation between the PLC.
Occupied
points
0 point (This number is not related to the ma
input/output points of the PLC.)
Device number
Description
BD1 BD2
Special
auxiliary
relay
M8260 M8270
Switches the output mode
OFF: Voltage output ON: Curre
M8264 M8274
Output Holding Function Ca
Setting
OFF: Holds the analog data outp
before stop of the PLC.
ON: Output the offset data at st
PLC.
Special
data
register
D8260 D8270 Output setting data
D8268 D8278
Error status
b0: Output data setting error
b1: Unused
b2: Unused
b3: Unused
b4: EEPROM error
b15 to b5: Unused
D8269 D8279 Model code = 4
Item
Specifications
Voltage output Curr
Analog output
Digital input
0 4080
10V
4000
Analog output
Dig
0
4mA
20mA