(1) Do not drop the module or cause it to receive strong impact.
(2) Do not remove the PCB of the module from its case.
Doing so may cause the module to fail.
(3) Always make sure to touch the grounded metal to discharge the
electricity charged in the body, etc., before touching the module.
Failure to do so may cause a failure or malfunctions of the module.
(4) Tighten the screws to the specified torque shown below.
Insufficient tightening torque could result in shorts, failures or
malfunction.
4.1 Mounting module fixing bracket
Hold the Q66DA-G with module fixing bracket after the Q66DA-G is
mounted to the base unit.
Screw location Tightening torque range
Module mounting screw (M3 screw) 0.36 to 0.48 N•m
FG terminal screw (M3 screw) 0.42 to 0.58 N•m
POINT
Make sure that the module fixing bracket is hooked on the 3rd slit