1. OVERVIEW
This manual describes the specifications and part names of the Q68TD-
G-H01 Channel Isolated Thermocouple Input channel isolated
thermocouple input module (hereinafter abbreviated referred to as
Q68TD-G-H01) that is used with the MELSEC-Q series CPU module.
1.1 Restrictions on mountable slot position
(1) Restriction of combination use of Q68TD-G-H01 and Q68TD-G-
H02
When mounting the Q68TD-G-H01 and Q68TD-G-H02 on the base
unit, leave one slot or more than one slot of space between the
Q68TD-G-H01 and the Q68TD-G-H02.
(2) Restrictions on mountable slot position of Q68TD-G-H01
The Q68TD-G-H01 has restrictions on mountable slot position.
The following describes the restrictions of the slot position when
mounting the Q68TD-G-H01 with a combination of the power
supply module and the base unit.
For the slot that the Q68TD-G-H01 cannot be mounted, leave the
slot open or mount a module other than the Q68TD-G-H01.
The Q68TD-G-H01 has no restrictions of the combination between
a power supply module and a base unit other than the combination
listed below.
When using the Q68TD-G-H01 on the remote I/O station, the
restriction is the same as for the main base unit.
When failing to comply with the following restrictions, the accuracy
might not be in the specification range.
Power supply module
Restrictions
Main base unit Extensio