当前位置:首页 >> 技术支持 >> QJ71C24 R2与E540通讯问题
QJ71C24 R2与E540通讯问题  时间:2014/3/7 16:35:00
QJ71C24 R2与E540变频器进行232通信,QJ发送后变频器无反应,在电脑上用串口调试工具发送同样的数据,变频器动作正常。将QJ的端口连接至电脑端口后用串口调试工具对其发送内容进行检测后发现并无错误,只是获得的数据并不是一起接收到得。先将串口调试工具获得的内容粘贴如下:
# Time Function Data ( Hex )
16 [00010541] IRP_MJ_READ Length: 0001, Data: 05
17 [00010541] IRP_MJ_READ Length: 0001, Data: 30
18 [00010541] IRP_MJ_READ Length: 0001, Data: 30
19 [00010541] IRP_MJ_READ Length: 0001, Data: 46
20 [00010541] IRP_MJ_READ Length: 0001, Data: 41
21 [00010541] IRP_MJ_READ Length: 0001, Data: 31
22 [00010541] IRP_MJ_READ Length: 0001, Data: 30
23 [00010541] IRP_MJ_READ Length: 0001, Data: 30
24 [00010541] IRP_MJ_READ Length: 0001, Data: 37
25 [00010541] IRP_MJ_READ Length: 0001, Data: 38
26 [00010542] IRP_MJ_READ Length: 0001, Data: 0D
27 [00010543] IRP_MJ_READ Length: 0001, Data: 0A
注:以上是串口调试工具获得QJ发送的数据记录,这个是变频停止指令(用串口调试工具让变频器先运转起来后再用此指令),即使是变频器运行指令,变频器也无反应。为什么接收来的数据时这个样子呢??而不是一个长度为12的数据呢??
138 [00003133] IRP_MJ_WRITE Length: 0012, Data: 05 30 30 46 41 31 30 32 37 41 0D 0A
139 [00003136] IRP_MJ_READ Length: 0003, Data: 06 30 30
140 [00004015] IRP_MJ_WRITE Length: 0012, Data: 05 30 30 46 41 31 30 30 37 38 0D 0A
141 [00004018] IRP_MJ_READ Length: 0003, Data: 06 30 30
142 [00007181] IRP_MJ_WRITE Length: 0012, Data: 05 30 30 46 41 31 30 32 37 41 0D 0A
143 [00007184] IRP_MJ_READ Length: 0003, Data: 06 30 30
注:以上是有串口调试工具向E540发送同样的数据 E540动作正常
通信设置 9600、8、 Even 、2。 QJ(SW3:05DE SW4:0006)、 E540(0号站 9600、8、even、2、CRLF结束符、通信次数为9999 )、串口调试工具均设置无误
Re:续:QJ71C24 R2与E540通讯问题  时间:2014/3/8 8:23:00
你好,正转及停止指令都没有问题,串口调试软件发送指令能正常动作说明变频器侧的参数设置都正确。建议确认使用QJ模块,相关程序是否正确。
感谢您对三菱电机自动化产品的支持,欢迎拨打400--免费技术热线,获取进一步的相关信息。

Re:Re:续:QJ71C24 R2与E540通讯问题  时间:2014/3/8 10:47:00
我的问题就是连接QJ后变频无反应, 所以我用电脑接收QJ的发的信息,看看有没错误,结果就出现了第一段所接收的那样的信息16—27段。
Re:Re:Re:续:QJ71C24 R2与E540通讯问题  时间:2014/3/8 15:35:00
根据您的说明,变频器侧的设定都没有问题。需要注意变频器与QJ模块间的设定是否匹配,其他相关问题建议询问Q PLC。
感谢您对三菱电机自动化产品的支持,欢迎拨打400--免费技术热线,获取进一步的相关信息。