广州菱控|三菱
当前位置:首页 >> 资料下载 >> 三菱 >> CC-Link模块 >> 三菱 CL1Y2 三菱-CL1Y2-T1D2S 用户 手册
三菱 CL1Y2 三菱-CL1Y2-T1D2S 用户 手册
所属类别:三菱 >> CC-Link模块
资料介绍:

Warranty
Mitsubishi will not be held liable for damage caused by factors found not to
cause of Mitsubishi; machine damage or lost profits caused by faults in the Mit
products; damage, secondary damage, accident compensation caused by
factors unpredictable by Mitsubishi; damages to products other than Mit
products; and to other duties.
For safe use
• This product has been manufactured as a general-purpose part for general
industries, and has not been designed or manufactured to be incorporated in
device or system used in purposes related to human life.
• Before using the product for special purposes such as nuclear power, electric
aerospace, medicine or passenger movement vehicles, consult with Mitsubis
• This product has been manufactured under strict quality control. However wh
installing the product where major accidents or losses could occur if the prod
This manual confers no industrial property rights or any rights of any other kin
does it confer any patent licenses. Mitsubishi Electric Corporation cannot b
responsible for any problems involving industrial property rights which may oc
a result of using the contents noted in this manual.
ment pressurized above the
ound the altitude of 0 m. If the
il.
n outside the control panel as
ng temperature, the ambient
y to which the equipment is
ation
shall not be considered.
shall not be considered.
esent
Number of times of
sweep
mplitude
10 times in each of
X, Y and Z directions
(for 80 min)
mm

sent
mplitude
mm

Y and Z directions
nt.
5.2 Output specifications
5.3 Performance specifications
Item Specification
Output method
Transistor output
(using module power supply in common) (sink)
Number of outputs 2 points
Isolation method Isolation with photocoupler
Rated load voltage 24V DC
Operating load voltage
range
Same as module power supply
Max. load current 0.1A/point 0.2 A/1 common
Max. inrush current 0.4A/10 ms
Leakage current at OFF 0.1mA or less/30V DC
Max. voltage drop at ON 1V or less (max.)/0.1A
Response
time
OFF→ON 1.0ms or less
ON→OFF 1.0ms or less
Surge suppression Zener diode
Common wiring method 2 point/1 common (1 point)
Internal protection for
outputs
Internal protection circuit none
Please connect the fuse in the connected load
outside.
Item Specification
Module
power
supply
Vol tage
20.4 to 28.8V DC (24V DC -15% to +20%)
Ripple ratio: Within 5%
Current
consumption
40mA (when all points are ON)
Initial current 70mA
Max. allowable
momentary power
failure period
PS1:1ms
Number of stations
occupied
4-, 8- or 16-point mode: 1 station
Noise durability
500Vp-p
Noise width: 1µs Cycle: 25 to 60 Hz
(by noise simulator)
Withstand voltage 500V AC for 1 min
Isolation resistance
10 MΩ or more between primary area (external
DC terminal) and secondary area (internal circuit)
by 500V DC megger
Protection class IP2X
I/O part connection method Connection with cable
6. Outside Dimensions
24G Y0 Y1 +24V
Unit: mm(inches)
20(0.79")
65(2.56") 500(19.69")
12(0.48")
500(19.69")