2.1 Key to numbered items on Terminal Layout diagram
1. 24V DC transmission power for the network is supplied by the stabilized power supply.
2. The shielded twisted pair cables connect the FX0N-16NT to the network. The SDA/SDB terminals
of the previous station should be connected to the RDA/RDB terminals of this station. The SDA/SDB
terminals of this station should be connected to the RDA/RDB terminals of the next station.
Keep these transmission cables away from all power cables. Do not allow power cables and
transmission cables to share the same duct.
3. Use one-point grounding (Class 3 ground, 100 Ω or less) for the shielding of the twisted pair
cable on the sending or receiving sides.
4. See section 3.6 for use of the ECM (Emergency Clear Mode) terminal.
2.2 Use of crimp-style terminals
Use crimp-style terminals of the indicated dimensions.
6.2 mm (0.24
inch) or less