三菱 FX3U 三菱-FX3U-ENET-L 用户 手册
所属类别:三菱 >> FX系列PLC
资料介绍:

1) It is confirmed whether the initial processing has been completed
normally.
2) All data communication currently being performed with external devices
is terminated, and close processing will be performed on all connections.
3) "0001H ", "0002H ", "0005H " or "0006H " is written to BFM#1600.
(Initial normal completion signal: BFM#27 "0001H ")
(Open completion signal: BFM#20480 "All OFF(0H)")
4) When re-initialization is completed, the value in BFM#1600 will be 8000H
(normal completion) or C000H (abnormal completion).
* If the re-initialization is completed abnormally, the error code is stored
in the following area.
Initial error code storage area (BFM#105)