Wiring
External wiring
e input terminals of the CL1X2-D1D3S operate while using the power
plied from the interface.
en connecting a sensor to the input terminal, use a sensor of the NPN
n collector transistor type.
ut wiring
Connection to sensor
hen using a two-wire type sensor y When using a three-wire type sensor
eplace * in the figure with the used input No.
es:
Bleeder resistor
When connecting a two-wire type sensor or input equipment having
parallel resistor, select a sensor or equipment whose leakage current is
1.7mA or less.
If the leakage current is more than 1.7mA, connect a bleeder resistor
obtained in the following calculation formula.
24G
DA
DB
+24V
DC DC
R
X1
X0
0.5A
+24V
24G
R
CL1X2-D1D3S
Isolation
Flat cable
dedicated
to CC-Link/LT
Flat cable
for I/O
Internal
circuit
. . .
Bleeder resistor *1
Connected to +24 V
cable
Sensor (NPN) Sensor (NPN)
X *
24G
X *
24G
Connected to +24 V
cable
Detection
circuit
Detection
circuit
5. Specifications
5.1 General specifications
Notes:
*1 The module cannot be used in an environment pressurized above the
atmospheric pressure which can be generated around the altitude of 0 m. If the
module is used in such an environment, it may fail.
Item Specification
Ambient
working
temperature
0 to 55°C (32 to 131°F)
Ambient storage
temperature
-25 to 75°C (-13 to 167°F)
Ambient
operating
humidity
5 to 95%RH: Dew condensation shall not be considered.
Ambient storage
humidity
5 to 95%RH: Dew condensation shall not be considered.
Vibration
resistance
When intermittent vibration is present
Number of times of
sweep
Frequency Acceleration Half amplitude
10 times in each of
X, Y and Z directions
(for 80 min)
10 to 57Hz − 0.075mm
57 to 150Hz 9.8m/s2 −
When continuous vibration is present
Frequency Acceleration Half amplitude
10 to 57Hz − 0.035mm
57 to 150Hz 4.9m/s2 −
Impact
resistance
147 m/s2, 3 times in each of X, Y and Z directions
Operating
atmosphere
Corrosive gas shall not be present.
Operating
altitude
2,000m(6561'8") or less (*1)
Installation
place
Inside control panel (*2)
Over-voltage
category
ΙΙ or less (*3)
Degree of
contamination
2 or less (*4)
5.2 Input specificatio
5.3 Performance spe
Item
Input method
Number of inputs
Isolation method
Rated input voltage
Rated input current
Operating voltage range
Max. simultaneous ON
input points
ON voltage/ON current
OFF voltage/OFF current
Input resistance
Response
time
OFF→O
ON→OF
Common wiring method
Item
Module
power
supply
Vol tage
Current
consumption
Initial current
Max. allowabl
momentary pow
failure period
Number of stations
occupied
Noise durability
Withstand voltage
Isolation resistance