广州菱控|三菱
当前位置:首页 >> 资料下载 >> 三菱 >> 触摸屏 >> 三菱 CL1X4 三菱-CL1X4-D1B2 用户 手册
三菱 CL1X4 三菱-CL1X4-D1B2 用户 手册
所属类别:三菱 >> 触摸屏
资料介绍:


Wa
Mi
ca
pro
fac
pro
• T
i
d
Th
do
re
a
4.2 Connection to sensor
Positive common (NPN)
• When using a two-wire type sensor y When using a three-wire type sensor
• When using a three-wire type sensor
(when using the power supply for sensor other than 24V DC)
Negative common (PNP)
• When using a two-wire type sensor y When using a three-wire type sensor
• When using a three-wire type sensor
(when using the power supply for sensor other than 24V DC)
Bleeder resistor *1
Connected to DC 24A terminal
COMB
Connected to DC 24A terminal
COMB
Detection
circuit
Sensor (NPN)
X *
Detection
circuit
X *
COMB
Detection
circuit
X *
COMB COMB
Bleeder resistor *1
Connected to DC 24A terminal Connected to DC 24A terminal
Detection
circuit
Sensor (PNP)
X *
Detection
circuit
X *
COMB
Detection
circuit
X *
4.3 Crimp-style terminal
For I/O wiring, use crimp-style terminals of the following dimensions.
Use a crimp-style terminal in a status in which no force is applied on the cable.
4.4 Module terminal screw
Tighten the terminal screws (M3 screws) on the terminal block with a tightening
torque of 42 to 58 N⋅cm.
5. Specifications
5.1 General specifications
Applicable crimp-
style terminal
• RAV1.25-3
• V1.25-3 (manufactured by JST Mfg. Co., Ltd.)
• 1.25-3 and TG1.25-3 (manufactured by NICHIFU Co., Ltd.)
Applicable wire size 0.3 to 1.25 mm2
6.2 mm (0.24" )
or less
6.2 mm (0.24" )
or less
Terminal
Terminal screw
Crimp-style
terminal
Terminal screw
Crimp-style
terminal
When wiring one cable to one terminal When wiring two cables to one terminal
Terminal
φ 3.2 (0.13") φ 3.2 (0.13")
Item Specification
Ambient
working
temperature
0 to 55°C (32 to 131°F)
Ambient storage
temperature
-25 to 75°C (-13 to 167°F)
Ambient
operating
humidity
5 to 95%RH: Dew condensation shall not be considered.
Ambient storage
humidity
5 to 95%RH: Dew condensation shall not be considered.
When intermittent vibration is present
Number of times of
sweep
*4 This index indicates the degree of conductive generating substances in the
environment in which the module is used. The degree of contamination 2
indicates that contamination is caused by generation of only non-conductive
substances.
In this degree, however, temporary conduction may be caused by accidental
condensation.
5.2 Input specifications
5.3 Performance specifications
Item Specification
Input method DC input (External power supply of the input part)
Number of inputs 4 points
Isolation method Isolation with photocoupler
Rated input voltage 24V DC
Rated input current Approx. 4 mA
Operating voltage range
20.4 to 28.8V DC (24V DC -15% to +20%)
Ripple ratio: Within 5%
Max. simultaneous ON
input points
100% (at 24V DC)
ON voltage/ON current 19 V or more/3 mA or more
OFF voltage/OFF current 11 V or less/1.7 mA or less
Input resistance 5.6 kΩ
Response
time
OFF→ON 0.5ms/1.5 ms or less (at 24V DC)
Selected by DIP switch (default value = OFF/1.5ms).
ON→OFF
0.5ms/1.5 ms or less (at 24V DC)
Selected by DIP switch (default value = OFF/1.5ms).
Common wiring method
4 points/1 common (2 points)
(terminal block two-wire type)
Item Specification
Module
power
supply
Vol tage
20.4 to 28.8V DC (24V DC -15% to +20%)
Ripple ratio: Within 5%
Current
consumption
40mA (when all points are ON)
Initial current 70mA
Max. allowable
momentary power
failure period
PS1:1ms
Number of stations
occupied
4-, 8- or 16-point mode: 1 station
6
49(1.93") 4.5(0.18") 40(1.58")
立即下载     
相关下载